猫先生千人斩最厉害三个角色,《丈夫常年不在家》日剧,中文字幕免费高清电视剧网站

CN / EN

PRODUCTS

Current transformer for three-phase meter-EHC-DCT Series for DC Immune
views:1865time:2020-07-21 11:40:35
EHC-DCT Series for DC Immune EHC-DCT Series for DC Immune
Features

Key Features/Application

l  overt alternative current or a half-wave rectifier DC current to accurate low-current

l  Suitable for GB/T17215.321 Electricity meters with DC and Even harmonic requirements

l  Encapsulated with epoxy resin, Power-frequency Withstand Voltages: 4000V/1min, 

          Insulation Resistance: ≥1000MΩ/500Vdc;

l  Working Frequency: 50Hz400Hz;

l  Operating Temperature: -40℃85℃.

l  Comply to JB/T10665-2016IEC61869-2-2012


Specifications

Only few typical products of this series are shown in the following pages. EHC is capable of making other customized design and manufacturing per user request.


Specifications

Model

Current Ratio

Rated Burden(Ω

Accuracy Class

EHC-DCT013

EHC-DCT038

EHC-DCT074

EHC-DCT111

5(60)A/2mA

5

10

20

0.05

0.1

10(60)A/4mA

EHC-DCT042

EHC-DCT050

EHC-DCT052

EHC-DCT108

5(100)A/2mA

10(100)A/4mA

10(120)A/4mA


TIM图片20200721113934.png



Half-Wave Rectifier (DC and Even harmonic) Test

 

In order to ensure the accuracy of measurement, the balanced impedance should be equal to the impedance of DUT. The same type of instrument as DUT is strongly recommended.

 

Half-Wave current contains Direct DC component, Fundamental harmonic and Even harmonic, the error of the Class 1 meter should be less than 3% and the error of Class 2 meter should be less than 6%.

image.png

modelEHC-DCT Series for DC Immune
Current transformer for three-phase meter
Download